Checklist

Cooling tower

Description Recommendation Maintenance frequency Implementation
Use/adjustment of operational order of the cooling towers Turn off/adjust the operational order of unnecessary cooling towers Daily  Yes 
Overall visual inspection Complete the overall visual inspection to ensure that all cooling towers are in good working conditions and safety systems are in the right place Daily  Yes 
Check for any obstruction Make sure the good water circulation in the cooling tower Daily  Yes 
Fan motor condition Check the condition of the fan motor based on temperature or analyze the vibration and compare it with the reference value. Weekly   Yes 
Clean the suction membrane  Clean up any deposits of the suction membrane  Weekly   Yes 
Check the water sample Check the appropriate concentration of dissolved solids and chemicals. Adjust blowdown level and chemical quantity if necessary. Weekly   Yes 
Operate the addition of water  Operate the manual switch to check the correct on-off control of the float valve Weekly   Yes 
Vibration Check the motor, fan and pump for any excessive vibration  Weekly   Yes 
Check the tower structure Check the connections and packings for any looseness, leaking points... Weekly   Yes 
Check the belt and pulley Adjust all the belts and pulleys  Weekly   Yes 
Check the lubricants Make sure that all shaft bearings are lubricated as recommended by the manufacturer Monthly  Yes 
Check the drive motor and propellers Check for excessive wear and ensure tightness Monthly  Yes 
Adjust the motor alignment  Align the coupling with the motor to increase transmission efficiency  Monthly  Yes 
Check the water partitions, air inlets and packings  Find suitable location and size for installation  Monthly  Yes 
Clean the tower Remove all dust, deposits and algae from water tanks, packings and nozzles Annually  Yes 
Check the shaft bearing Check the drive belt and shaft bearing for wear and tear.
Adjust, repair or replace when needed.
Annually  Yes 
Motor condition Check motor condition through temperature or vibration analysis in order to ensure a long service life Annually  Yes 

Attachments :

Để có thể bình luận, xin vui lòng đăng nhập

Boiler

24/12/2020

Checklist for Boiler

Steam Trap

24/12/2020

Checklist for Steam Trap

Chiller

24/12/2020

Checklist for Chiller

Air handling system

24/12/2020

Checklist for Air handling system

Control of the building

24/12/2020

Checklist for Control of the building

Lighting

22/12/2020

Checklist for Lighting